Reed level sensor: Defining the measuring range flexibly

A float-based level sensor with a reed chain is a widely used and comparatively economical solution for continuous level measurement in vessels. Users can define its measuring range flexibly within a given range. This short article describes what must be taken into account.
With a reed-chain level sensor, the guide tube contains a defined amount of reed contacts, based on the measuring range. They are combined to create a measuring chain. The contacts react to the magnetic field of the float, which moves within the guide tube based on the liquid level.
Accuracy depends on the distance between the contacts
The accuracy of this energy-free level monitoring depends, subsequently, on the distance between your individual contacts: small it is, the more accurate the measurement. Each level sensor in WIKA?s RLT series, for instance, enables measuring ranges with contact distances between 3 and 24 mm. However, a reed chain can’t be stretched along the entire length of the guide tube. It is because you can find ?dead bands? at Uncomfortable of the tube, i.e. sections that the float does not detect due to design constraints (see graphic).
The graph shows how the maximum possible measuring range (M) having an air-handling series level sensor is defined: Guide tube length (L) minus dead band (T) and 100 % mark (X).
Maximum measuring range is not a must
The measuring range of an even sensor therefore lies between your two dead bands specified in the info sheet. In this range, it might be freely defined. However, it really is by no means necessary to utilise the utmost possible measuring range in every applications. The exact adaptation of the amount of contacts to the measuring task also offers an economic advantage: The reed chain is probably the most expensive components in an even sensor.
Example ? Dry run monitoring
For dry run monitoring within an oil tank of a compressor, for instance, only the lower the main guide tube is needed for the measurement. In this instance, top of the measuring point of the application (100 % mark) is set correspondingly low. Under Priced marks the distance to the sealing face of the procedure connection. The measuring range is thus defined by the following equation:
Measuring range length M = guide tube length L ? dead band T ? 100 % mark X
Consequently, the measuring range for detecting a maximum level is set starting from the sealing face. In this instance, the guide tube could be adapted to along the measuring range.
Note
More info on the RLT series level sensors are available on the WIKA website. Assuming you have any questions, your contact will gladly assist you to.